HTP100 100W Plastic Enclosure Heater 110-240V AC/DC Terminal Block IP20

SKU
HTP100
Buy 15 for £73.85 each and save 5%
  £77.74
tick Lead time variable - contact us on 01782 349 430
View Downloads chevron-right
SKU HTP100
Lead Times variable - contact us on 01782 349 430
Manufacturer FANDISEU
Heating Power (W) 100
Rated Voltage 110-240V a.c/d.c.
Wiring Type Terminal
Heater Type Plastic with Terminal Block

Description

Fandis HTP100 PTC Enclosure Heater

The Fandis HTP100 is a compact DIN rail mounted enclosure heater designed to prevent condensation and maintain reliable operating temperatures within electrical cabinets and control panels. It incorporates a self-regulating PTC heating element and a black anodised extruded aluminium heat sink for efficient and safe heat distribution.

 

Key Features of the HTP100:

  • Heating element: PTC thermistor, self regulating
  • Heat sink: black anodised extruded aluminium profile black PET; in case of accidental contact, the surface material of the plastic heater prevents the danger of burns
  • Method of mounting: snap-on fixing on RAIL 35mm EN 50022
  • Rated temperature range: from -30°C to +40°C
  • Storage temp. range from -40°C to +70°C
  • Protection degree by heaters: IP20 
  • Dimensions (mm): 188x85x61.5 
  • Electrical connection:by 3 poles terminal L-N-PE 3 clamps for solid or fine stranded wire 0.5 ÷ 2.5mm2 (20 ÷ 16 AWG)
  • Appliance class: class l
  • Rated voltage range: 110-240 V a.c./d.c.
  • Rated frequency: 50/60 Hz
  • Max voltage: 265 V a.c./d.c.
  • Applicable standards: EN 60335-1
  • Approvals: CE; cURus certified till max 50°C

 

View the full range of Fandis enclosure heaters.

 

The formation of condensation is one of the biggest dangers for electrical enclosures and cabinets. Provided that they are working under load, their own heat prevents the condensing of fluids. If the process is switched off, the electronics cool down. This is precisely where the function of our control cabinet heaters begins to protect. 


Our heaters are used in combination with an enclosure thermostat (Normally Closed) or cabinet hygrostat, predominantly for the avoidance of excessively low temperatures or excessively high humidity in the control cabinet and help to avoid the formation of corrosion.

 

Shop our range of normally closed thermostats, to detect when to turn on a heater within the enclosure, available for next working day delivery.